Dynamic selective harmonic elimination of a three-level inverter used for static VAr compensation (2002)
Journal Article
Ran, L., Holdsworth, L., & Putrus, G. (2002). Dynamic selective harmonic elimination of a three-level inverter used for static VAr compensation. IEE proceedings. Generation, transmission and distribution, 149(1), 83-89. https://doi.org/10.1049/ip-gtd%3A20020082

The paper investigates the harmonic interaction between the AC and DC sides of a 3-level inverter used as a static synchronous VAr compensator (STATCOM). It is illustrated that due to the 3rd harmonic voltage across each DC side capacitor. the conven... Read More about Dynamic selective harmonic elimination of a three-level inverter used for static VAr compensation.